When you plug in an electric device, it’s
easy not to even consider where the electricity actually comes from. The simple answer is a power generating station,
also known as a power plant, usually someplace far away. But the reality is much more complicated than
that. Generation is only the first of many steps
our power takes on its nearly instantaneous journey from production to consumption. The behaviour of electricity doesn’t always
follow our intuitions, which means the challenges associated with constructing, operating, and
maintaining the power grid are often complicated and sometimes unexpected. Many of those challenges are overcome at facility
which, at first glance, often looks like a chaotic and dangerous mess of wires and equipment,
but which actually serves a number of essential roles in our electrical grid, the substation. I’m Grady and this is Public Works, my video
series on infrastructure and the humanmade world around us. This video is sponsored by NordVPN. Visit NordVPN.com/practicalengineering to
get 75% off a 3-year plan. More on that later. As simple as it is to imagine, the power grid
isn’t just an interconnected series of wires to which all power producers and users collectively
connect. In reality, the electricity normally makes
its way through a series of discrete steps on the grid normally divided into three parts:
generation, or production of electricity; transmission, or moving that electricity from
centralized plants to populated areas; and distribution, or delivering the electricity
to every individual customer. If you consider the power grid a gigantic
machine (and many do), substations are the linkages that connect the various components
together. One of the cool parts about our electrical
infrastructure is that most of it is out in the open so anyone can have a look. I’m somewhat of an infrastructure tourist,
a regular beholder of the constructed environment, and my goal is for you too to be able to mentally
untangle this maze of modern electrical engineering so that the next time you feast your eyes
on a substation, you’ll be able to appreciate it as much as I do. Originally named for smaller power plants
that were converted for other purposes, “substation” is now a general term for a facility that
can serve a wide variety of critical roles on the power grid. Those roles depend on which parts of the electrical
grid are being connected together and the types, number, and reliability requirements
of the eventual customers downstream. And the first and often simplest of these
roles is switching. The general layout of a substation consists
of some number of electric lines (called conductors if you want to fit in with the electrical
engineers) coming into the facility. These high voltage conductors connect to a
series of some or many pieces of equipment before heading out to their next step in the
power grid. As a junction point in the grid, a substation
often serves as the termination of many individual power lines. This creates redundancy, making sure that
the substation stays energized even if one transmission lines goes down. But, it also creates complexity. The connections to these various devices are
called buses, often rigid, overhead conductors that run along the entire substation. The arrangement of the bus is a critical part
of the design of any substation because it can have a major impact on the overall reliability. Like all equipment, substations occasionally
have malfunctions or things that simply require regular maintenance. To avoid shutting down the entire substation,
we need switches that can isolate equipment, transfer load, and control the flow of electricity
along the bus. This may seem obvious, but turning on and
off high voltage lines isn’t as simple as flipping a light switch. At high voltages, even air can act like a
conductor, which means even if you create a break in a line, electricity can continue
flowing in a phenomenon known as an arc. Not only does arcing defeat the purpose of
a switch, it is incredibly dangerous and damaging to equipment. So, switching in a substation is a carefully-controlled
procedure with specially-designed equipment to handle high voltages. Disconnect switches are often just called
switchgear in addition to the equipment that serves another important role in a substation:
protection. I mentioned earlier that much of our electrical
infrastructure is exposed and out in the open. That’s nice for people like me who enjoy
having a look, but it also means being vulnerable to an endless number of things that can go
wrong. From lightning strikes to rogue tree limbs,
windstorms to squirrels, grid operators contend with so many threats to their infrastructure
on a day by day basis. When something causes a short circuit on the
power grid, also called a fault, it can severely damage power lines and other equipment. Not only that, because of the overwhelming
complexity of the power grid, faults can and do cascade in unexpected and sometimes uncontrollable
ways, leaving huge populations without power for hours or days. Many of the ways we protect equipment from
faults are handled at a substation. One of the most common types of electrical
fault is a short circuit to ground. This type of fault creates a low-resistance
path for current to flow and leads to an overload of power lines and equipment. The simplest way to protect against this type
of fault is with a fuse, a device that physically burns out at a certain current threshold. Fuses are dead simple and don’t require
much maintenance, but they have some disadvantage too. They’re one-time use and can’t be used
to interrupt current for other types of faults. On the other hand, circuit breakers are a
class of devices that serve similar roles as fuses, but provide more sophistication
for dealing with a wide variety of faults. Like disconnect switches, circuit breakers
need to be carefully designed to interrupt huge voltages and currents without damage. As soon as contacts within a circuit breaker
are moved apart from one another, an electrical arc forms. This arc needs to be extinguished as quickly
as possible to prevent damage to the breaker or unsafe conditions for workers. Extinguishing the arc is accomplished by a
material called a dielectric that doesn’t conduct electricity. For lower voltages, the circuit breakers can
be located in a sealed container under vacuum to avoid electricity conducting in the air
between the contacts. For higher voltage, breakers are often submerged
in tanks filled with non-conductive oil or dense dielectric gas. These breakers give grid operators more control
about how and when current gets interrupted. Not every fault is the same and sometimes
operators even know about a disturbance ahead of time and can trigger breakers early to
prevent cascading failures. Many faults are temporary like lightning strikes
or swaying tree branches. A special kind of circuit breaker called a
recloser can interrupt current for a short period of time and re-energize the line to
test if the fault has cleared. Re-closers usually trip and reclose a few
times, depending on their programming, before deciding that a fault is permanent and locking
out. If electricity demand on the grid gets so
high that it can’t be met by the utility, substations may also be used to shed load. Rolling blackouts are used to lower the total
electrical demand to avoid bigger failures on the grid. One of the most important parts of the power
grid is that different segments flow at different voltages. Voltage is a measure of electrical potential,
somewhat equivalent to the pressure of a fluid in a pipe. At large power plants, electricity is produced
at a somewhat low voltage of around 10-30 kilovolts or kV. From there, the voltage is increased much
higher using transformers so that it can travel along transmission lines. Using a higher voltage reduces the losses
along the way, making them more efficient but also much more dangerous. This is why overhead transmission lines are
so tall - to keep them out of the way of trees and human activities. But, when transmission lines reach the populated
areas which they serve, it’s not feasible to keep them so high in the air. So, prior to distribution, the voltage of
the grid needs to be brought back down, again using transformers located within a substation. A transformer is an extremely simple device
that relies on the alternating current of the grid to function. It consists of two adjacent coils of wire. As the voltage in one coil changes, it creates
a magnetic field. This field couples with the other coil, inducing
a voltage. The incredible part of a transformer has to
do with the number of loops in each coil. The induced voltage will be proportional to
the ratio of loops. For example, if the transmission side of a
transformer has 1000 loops while the distribution side has 100, the voltage on the distribution
side will be 10 times less. This simple but incredible fact makes it possible
for us to step up or down voltage as necessary to balance the safety and efficiency along
each part of the power grid. The simplicity of transformers is great in
a lot of ways, but it also means that it can be difficult to make fine adjustments to the
power leaving the substation. Because of this, many many substations include
equipment for monitoring and controlling the power on the grid. Instrument transformers are small transformers
used to measure the voltage or current on the grid or provide power to system monitoring
devices. Depending on varying transmission and distribution
losses, the voltage on the grid can swing outside an acceptable range. Regulators are devices with multiple taps
that can make small adjustments - up or down - to the distribution voltage on feeder lines
leaving the substation toward customers. If you look closely you can sometimes see
the regulator dial indicating the tap position. All that different equipment requires lots
of maintenance. The final and most important role of a substation
is that it be safe for electricians and linemen to inspect, repair, and replace equipment. Substations are usually the only locations
where extra-high voltage power lines get close to the ground, so safety is absolutely critical. The buswork running along the substation is
protected from short-circuit by large insulators to avoid arcs to ground. Even the connections into each piece of equipment
are done through a device called a bushing which maintains a safe distance between energized
lines and the grounded metal housings. Some substations have large concrete walls
to serve as fire barriers between equipment. All substations are built with a grid of grounding
rods and conductors buried below the surface. In the event of a fault, the substation needs
to be able to sink lots of current into the ground to trip the breakers as quickly as
possible. This grounding grid also makes sure that the
entire substation and all its equipment are kept at the same voltage level, called an
equipotential, so that touching any piece of equipment doesn’t create a flow of electricity
through a person. Finally, substations are surrounded by large
fences and warning signs to make absolutely sure that any wayward citizens know to stay
out. In many ways, the grid is a one-size-fits-all
system - a gigantic machine to which we all connect spinning in perfect synchrony across,
in some cases, an entire continent. On the other hand, our electricity needs,
including when we need it, how much we need, and how reliably it should be delivered vary
widely. Power requirements are vastly different between
a sensitive research facility and a suburban residential neighborhood, between a military
base and country club golf course, and between a steel mill and a bowling alley. Likewise, every electrical substation is customized
to meet the needs of the infrastructure it links together. As the grid gets smarter, as demand patterns
change, and as we (hopefully!) continue to replace fossil fuel generation with sources
of renewable energy to curb global warming, managing our electrical infrastructure will
only get more challenging. So, substations will continue to play a critical
role in controlling and protecting the power grid. Just like electricity on the grid, internet
traffic goes through several steps along the way. As I sat in an airport writing this video,
I was definitely wondering if one of those steps might be a hacker or organization recording
my traffic. Unfortunately, people have come up with lots
of ways to intercept web traffic and use that information nefariously, which is why I use
NordVPN. Some web traffic is already encrypted, but
I don’t want to keep track of whatever protocol each website or service happens to be using. NordVPN makes it super simple to make absolutely
sure I’m protected. I just load the app, click connect and it’s
done. There’s no limit on bandwidth, and it works
on all my devices. I don’t leave my house unlocked when I’m
away, even though I know the likelihood of someone trying to break in is low. And even though there’s probably not someone
sniffing packets at my local coffee shop, I don’t use their wifi (or any other public
network) without using NordVPN. It’s just not worth the risk. If your privacy and security online is important
to you, they’re offering an awesome discount to fans of the channel. Visit NordVPN.com/practicalengineering or
click the link in the description below to get 75% off a 3-year plan. Use promo code PracticalEngineering to get
an extra month for free. Thank you for watching, and let me know what
you think!
It's nice that he included a small mention of reclosers. Those little guys are so useful for keeping branch circuits up during storms and temporary tree branch faults. They are often pole mounted out on the circuit too so multiple ones working together can isolate a fault and re-close as much of the circuit as possible.
Ever seen your the power briefly try to turn back on 30 or 45 seconds after an outage? That's why! (usually)
They usually include some combination of switches, transformers, and protective devices (fuses or breakers).
Incoming power (usually one source) can be switched to any number of destination circuits at a possibly different voltage. Protective devices automatically disconnect circuits to prevent damage from overloads or lightning.
Modern substation equipment is monitored and controlled at central locations.
Wow thank you for posting this. I’ve always been curious on how substations work and what a lot of the funny-looking instrumentation is for. Very helpful information.
I work in substations, currently putting together a new 3000A bus @ 15kV. Very cool stuff.
Very interesting watch! Does anyone know a vid that gets more into detail?
Overall very good info, but did not like the part where he talked about oil circuit breakers. I do not know of any utilities that still use these over SF6 puffer or puff-assist breakers.